Product Details | CIRCUIT BREAKER

5925-01-024-3342 A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.

Part Alternates: 5925-01-024-3342, 01-024-3342, 5925010243342, 010243342

Electrical and Electronic Equipment Components | Circuit Breakers

Supply Group (FSG) NSN Assign. NIIN
59 01-024-3342

Drawings & Photos | NSN 5925-01-024-3342


Cross Reference | NSN 5925-01-024-3342

Part Number Cage Code Manufacturer
M55629/7-065 81349 MILITARY SPECIFICATIONS PROMULGATED BY MILITARY
MIL-C-55629/7 81349 MILITARY SPECIFICATIONS PROMULGATED BY MILITARY
UPG-6-1-51-802 81541 SENSATA TECHNOLOGIES MARYLAND, INC

Request a Quote

What Our Customers Say

Compare

NSNs for Compare ( up to 4 ): Add 5925-01-024-3342

Technical Data | NSN 5925-01-024-3342

Characteristic Specifications
POLE QUANTITY 1
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 8.0 AMPERES DC SINGLE LOCATION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 65.0 DC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 2000.0 DC SINGLE LOCATION
CIRCUIT PROTECTION TYPE OVERCURRENT SINGLE LOCATION
TRIP RELEASE METHOD MAGNETIC-HYDRAULIC SINGLE LOCATION
INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP SINGLE LOCATION
TRIP RELEASE CHARACTERISTIC TIME DELAY SINGLE LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 1.000 MINIMUM AT 200 PCT AND 10.000 MAXIMUM AT 200 PCT SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 SINGLE LOCATION
RESET METHOD MANUAL
MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
BODY STYLE 12A SINGLE POLE TYPE
BODY LENGTH 1.985 INCHES MINIMUM AND 2.015 INCHES MAXIMUM
BODY WIDTH 0.735 INCHES MINIMUM AND 0.765 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 1.515 INCHES MINIMUM AND 1.545 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 1.645 INCHES MINIMUM AND 1.675 INCHES MAXIMUM
BOSS HEIGHT 0.115 INCHES MINIMUM AND 0.145 INCHES MAXIMUM
MOUNTING SURFACE TO TERMINAL END DISTANCE 2.032 INCHES MAXIMUM
CASE MATERIAL PLASTIC
MOUNTING FACILITY TYPE AND QUANTITY 2 THREADED HOLE
THREAD SERIES DESIGNATOR UNC
NOMINAL THREAD SIZE 0.138 INCHES
THREAD QUANTITY PER INCH 32
MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
ACTUATOR FUNCTION TRIP-RESET
ACTUATOR POSITION DESIGNATION AT POLE ONE
TERMINAL TYPE AND QUANTITY 2 SCREW
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED MOISTURE RESISTANT AND SALT SPRAY PROOF AND SHOCK RESISTANT AND VIBRATION RESISTANT
III ARC QUENCHING METHOD MAGNETIC BLOWOUT
III STORAGE TYPE GENERAL PURPOSE WAREHOUSE
III UNPACKAGED UNIT WEIGHT 2.200 OUNCES
III SPECIAL HANDLING FEATURE MAGNETIC
III FRAGILITY FACTOR MODERATELY RUGGED

Restrictions/Controls & Freight Information | NSN 5925-01-024-3342

Category Code Description
Hazardous Material Indicator CodePThere is no information in the HMIS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product
Category Code Description
No Freight Information