NSN 5925-01-020-9498 01-020-9498, 010209498
Product Details | CIRCUIT BREAKER
5925-01-020-9498 A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.
Part Alternates: 5925-01-020-9498, 01-020-9498, 5925010209498, 010209498
Electrical and Electronic Equipment Components | Circuit Breakers
Supply Group (FSG) | NSN Assign. | NIIN | Item Name Code (INC) |
---|---|---|---|
59 | 01-020-9498 | 00136 ( CIRCUIT BREAKER ) |
Request a Quote
What Our Customers Say
Compare
Related Products | NSN 5925-01-020-9498
Technical Data | NSN 5925-01-020-9498
Characteristic | Specifications |
---|---|
POLE QUANTITY | 3 |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 20.0 AMPERES AC AND 20.0 AMPERES DC ALL LOCATIONS |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC AND 250.0 DC ALL LOCATIONS |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 15000.0 AC AND 10000.0 DC ALL LOCATIONS |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 11.000 MINIMUM AT 200 PCT AND 35.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
RESET METHOD | MANUAL |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
BODY STYLE | 11B MULTIPOLE-SINGLE ACTUATOR TYPE |
BODY LENGTH | 6.062 INCHES NOMINAL |
BODY WIDTH | 4.125 INCHES NOMINAL |
BODY HEIGHT | 3.406 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 5.219 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.375 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 5.125 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.375 INCHES NOMINAL |
BOSS HEIGHT | 0.250 INCHES NOMINAL |
CASE MATERIAL | PLASTIC |
MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
UNTHREADED MOUNTING HOLE DIAMETER | 0.225 INCHES NOMINAL |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE TWO |
TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
III STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
Restrictions/Controls & Freight Information | NSN 5925-01-020-9498
Category | Code | Description |
---|---|---|
Hazardous Material Indicator Code | P | There is no information in the HMIS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product |
Category | Code | Description |
---|---|---|
No Freight Information |