Product Details | CIRCUIT BREAKER

5925-01-019-8910 A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.

Part Alternates: THED136070XL, 5925-01-019-8910, 01-019-8910, 5925010198910, 010198910

Electrical and Electronic Equipment Components | Circuit Breakers

Supply Group (FSG) NSN Assign. NIIN
59 20 APR 1976 01-019-8910

Drawings & Photos | NSN 5925-01-019-8910


Cross Reference | NSN 5925-01-019-8910

Part Number Cage Code Manufacturer
THED136070XL 60969 GENERAL ELECTRIC CO ELECTRICAL DISTRIBUTION AND CONTROL

Request a Quote

What Our Customers Say

Compare

NSNs for Compare ( up to 4 ): Add 5925-01-019-8910

Technical Data | NSN 5925-01-019-8910

Characteristic Specifications
POLE QUANTITY 3
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 70.0 AMPERES AC ALL LOCATIONS
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 600.0 AC AND 250.0 DC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 18000.0 AC AND 20000.0 DC ALL LOCATIONS
CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
TRIP RELEASE METHOD THERMAL-MAGNETIC ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING 10.0 DEG CELSIUS MINIMUM AND 50.0 DEG CELSIUS MAXIMUM ALL LOCATIONS
TRIP RELEASE CHARACTERISTIC INSTANTANEOUS AND TIME DELAY ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 88.000 MINIMUM AT 200 PCT AND 350.000 MAXIMUM AT 200 PCT AND 27.500 MINIMUM AT 300 PCT AND 140.000 MAXIMUM AT 300 PCT AND 14.500 MINIMUM AT 400 PCT AND 77.500 MAXIMUM AT 400 PCT AND 7.500 MINIMUM AT 500 PCT AND 47.500 MAXIMUM AT 500 PCT ALL LOCATIONS
RESET METHOD MANUAL
MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
BODY STYLE 13B MULTIPOLE-SINGLE ACTUATOR TYPE
BODY LENGTH 6.3125 INCHES NOMINAL
BODY WIDTH 4.125 INCHES NOMINAL
BODY HEIGHT 3.1875 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 4.87501 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 1.375 INCHES NOMINAL
BOSS HEIGHT 0.90625 INCHES NOMINAL
CASE MATERIAL PLASTIC
MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
ACTUATOR FUNCTION RESET
TERMINAL TYPE AND QUANTITY 3 SCREW BASE
FEATURES PROVIDED ADJUSTABLE TRIP RELEASE AND INTERCHANGEABLE TRIP RELEASE

Restrictions/Controls & Freight Information | NSN 5925-01-019-8910

Category Code Description
Hazardous Material Indicator CodePThere is no information in the HMIS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product
Demilitarization Code:ANon-Munitions List Item/ Non-Strategic List Item - Demilitarization not required.
Precious Metals Indicator Code:UPrecious metal type is unknown
Criticality Code:X The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
Category Code Description
No Freight Information