Product Details | CIRCUIT BREAKER

5925-00-931-5940 A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.

Part Alternates: AM171032VDC55, AM17-10-32VDC55, 5925-00-931-5940, 00-931-5940, 5925009315940, 009315940

Electrical and Electronic Equipment Components | Circuit Breakers

Supply Group (FSG) NSN Assign. NIIN
59 00-931-5940

Drawings & Photos | NSN 5925-00-931-5940


Demand History | NSN 5925-00-931-5940

Part Number Request Date QTY Origin
5925-00-931-5940 2010-06-169 1 US

Request a Quote

What Our Customers Say

Compare

NSNs for Compare ( up to 4 ): Add 5925-00-931-5940

Technical Data | NSN 5925-00-931-5940

Characteristic Specifications
POLE QUANTITY 1
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 10.0 AMPERES DC SINGLE LOCATION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 32.0 DC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 3000.0 DC SINGLE LOCATION
CIRCUIT PROTECTION TYPE OVERCURRENT SINGLE LOCATION
TRIP RELEASE METHOD MAGNETIC-HYDRAULIC SINGLE LOCATION
INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP SINGLE LOCATION
TRIP RELEASE CHARACTERISTIC TIME DELAY SINGLE LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 2.400 MINIMUM AT 200 PCT AND 7.500 MAXIMUM AT 200 PCT SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 150.0 SINGLE LOCATION
RESET METHOD MANUAL
MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
BODY STYLE 4A SINGLE POLE TYPE
BODY LENGTH 2.500 INCHES NOMINAL
BODY WIDTH 0.750 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 1.190 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 1.812 INCHES NOMINAL
MOUNTING SURFACE TO TERMINAL END DISTANCE 2.000 INCHES NOMINAL
CASE MATERIAL PLASTIC
MOUNTING FACILITY TYPE AND QUANTITY 2 THREADED HOLE
THREAD SERIES DESIGNATOR UNC
NOMINAL THREAD SIZE 0.138 INCHES
THREAD QUANTITY PER INCH 32
MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
ACTUATOR FUNCTION TRIP-RESET
ACTUATOR POSITION DESIGNATION AT POLE ONE
TERMINAL TYPE AND QUANTITY 2 SCREW
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED EXPLOSION RESISTANT
III ARC QUENCHING METHOD MAGNETIC BLOWOUT
III STORAGE TYPE GENERAL PURPOSE WAREHOUSE
III SPECIAL HANDLING FEATURE MAGNETIC
III FRAGILITY FACTOR MODERATELY RUGGED

Restrictions/Controls & Freight Information | NSN 5925-00-931-5940

Category Code Description
Hazardous Material Indicator CodePThere is no information in the HMIS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product
Category Code Description
No Freight Information