NSN 5925-00-755-5686 XAM44MG316220VAC505, XAM44MG3-1-6-220VAC50-5, 00-755-5686
Product Details | CIRCUIT BREAKER
5925-00-755-5686 A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.
Part Alternates: XAM44MG316220VAC505, XAM44MG3-1-6-220VAC50-5, 5925-00-755-5686, 00-755-5686, 5925007555686, 007555686
Electrical and Electronic Equipment Components | Circuit Breakers
Supply Group (FSG) | NSN Assign. | NIIN | Item Name Code (INC) |
---|---|---|---|
59 | 00-755-5686 | 00136 ( CIRCUIT BREAKER ) |
Request a Quote
What Our Customers Say
Compare
Related Products | NSN 5925-00-755-5686
Technical Data | NSN 5925-00-755-5686
Characteristic | Specifications |
---|---|
POLE QUANTITY | 2 |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 1.6 AMPERES AC ALL LOCATIONS |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 220.0 AC ALL LOCATIONS |
FREQUENCY IN HERTZ | 50.0 ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC ALL LOCATIONS |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP W/AUXILIARY LOAD TERMINAL ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.800 NOMINAL AT 200 PCT AND 0.300 NOMINAL AT 300 PCT ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
RESET METHOD | MANUAL |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
BODY STYLE | 8C MULTIPOLE-MULTIPLE ACTUATOR TYPE |
BODY LENGTH | 2.500 INCHES NOMINAL |
BODY WIDTH | 1.500 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.938 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.062 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES NOMINAL |
BOSS HEIGHT | 0.140 INCHES NOMINAL |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.471 INCHES NOMINAL |
CASE MATERIAL | PLASTIC |
MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE |
THREAD SERIES DESIGNATOR | UNC |
NOMINAL THREAD SIZE | 0.138 INCHES |
THREAD QUANTITY PER INCH | 32 |
MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT EACH POLE |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
TERMINAL TYPE AND QUANTITY | 4 THREADED STUD AND 2 TAB, SOLDER LUG |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | MOISTURE RESISTANT AND FUNGUS RESISTANT |
III ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
III STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
III UNPACKAGED UNIT WEIGHT | 8.750 OUNCES |
Restrictions/Controls & Freight Information | NSN 5925-00-755-5686
Category | Code | Description |
---|---|---|
Hazardous Material Indicator Code | P | There is no information in the HMIS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product |
Category | Code | Description |
---|---|---|
No Freight Information |