5925-00-755-5107 A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.
Part Alternates: PCB527PT3X11635K, 64964DMG445AMP, 64-964DMG4-45AMP, 9081266, 5925-00-755-5107, 00-755-5107, 5925007555107, 007555107
Electrical and Electronic Equipment Components | Circuit Breakers
Supply Group (FSG) | NSN Assign. | NIIN | Item Name Code (INC) |
---|---|---|---|
59 | 01 JAN 1962 | 00-755-5107 | 00136 ( CIRCUIT BREAKER ) |
Request a Quote
What Our Customers Say
Compare
Related Products | NSN 5925-00-755-5107
Technical Data | NSN 5925-00-755-5107
Characteristic | Specifications |
---|---|
POLE QUANTITY | 3 |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 45.0 AMPERES AC ALL LOCATIONS |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 416.0 AC ALL LOCATIONS |
FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1500.0 AC ALL LOCATIONS |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 3.000 MINIMUM AT 200 PCT AND 7.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
RESET METHOD | MANUAL |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
BODY STYLE | 5C MULTIPOLE-MULTIPLE ACTUATOR TYPE |
BODY LENGTH | 5.250 INCHES NOMINAL |
BODY WIDTH | 4.500 INCHES NOMINAL |
BODY HEIGHT | 2.687 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 4.359 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.987 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 3.062 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.987 INCHES NOMINAL |
BOSS HEIGHT | 0.218 INCHES NOMINAL |
CASE MATERIAL | PLASTIC |
MOUNTING FACILITY TYPE AND QUANTITY | 12 THREADED HOLE AND 12 UNTHREADED HOLE |
THREAD SERIES DESIGNATOR | UNC |
NOMINAL THREAD SIZE | 0.164 INCHES |
THREAD QUANTITY PER INCH | 32 |
UNTHREADED MOUNTING HOLE DIAMETER | 0.190 INCHES NOMINAL |
MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT EACH POLE |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
TERMINAL TYPE AND QUANTITY | 6 TAB W/SCREW |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF AND FUNGUS PROOF |
III ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
III STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
III SPECIAL HANDLING FEATURE | MAGNETIC |
III FRAGILITY FACTOR | MODERATELY RUGGED |
Restrictions/Controls & Freight Information | NSN 5925-00-755-5107
Category | Code | Description |
---|---|---|
Hazardous Material Indicator Code | P | There is no information in the HMIS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product |
Demilitarization Code: | A | Non-Munitions List Item/ Non-Strategic List Item - Demilitarization not required. |
Precious Metals Indicator Code: | U | Precious metal type is unknown |
Criticality Code: | X | The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application. |
Category | Code | Description |
---|---|---|
NMF Description | 061300 | CIRCUIT BREAKER/SWITCH NOI |
Less than car load rating | P | 77.5 |
Less than truck load rating | P | 77.5 |
Water commodity Code | 658 | unknown |
Originating Activity Code | XX | |
Air Dimension Code | A | Shipment is not a consolidation and does not exceed 72 inches in any dimension. |
Air Commodity | H | Signal Corps supplies and equipment, including radio equipment and supplies, communications equipment and supplies, electrical equipment and supplies, etc. |
Air Special Handling | Z | No special handling required. |
Special Handling Code | 9 | unknonwn |
HAZMAT | ||
Type of Cargo | Z | No special type of cargo code applicable |