Product Details | CIRCUIT BREAKER

5925-00-752-6903 A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.

Part Alternates: C9115230, C9115-2-30, MILC13516TYPE2GRADEACLASS1, 7526903, 5925-00-752-6903, 00-752-6903, 5925007526903, 007526903

Electrical and Electronic Equipment Components | Circuit Breakers

Supply Group (FSG) NSN Assign. NIIN
59 01 JAN 1962 00-752-6903

Drawings & Photos | NSN 5925-00-752-6903


Cross Reference | NSN 5925-00-752-6903

Part Number Cage Code Manufacturer
7526903 19207 U S ARMY TANK AUTOMOTIVE COMMAND AMSTA-IM-MM
C9115-2-30 82647 SENSATA TECHNOLOGIES, INC DIV SENSATA ATTLEBORO
MILC13516TYPE2GRADEACLASS1 81349 MILITARY SPECIFICATIONS PROMULGATED BY MILITARY

Request a Quote

What Our Customers Say

Compare

NSNs for Compare ( up to 4 ): Add 5925-00-752-6903

Technical Data | NSN 5925-00-752-6903

Characteristic Specifications
POLE QUANTITY 1
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 15.0 AMPERES DC SINGLE LOCATION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 30.0 DC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 600.0 DC SINGLE LOCATION
CIRCUIT PROTECTION TYPE OVERCURRENT SINGLE LOCATION
TRIP RELEASE METHOD THERMAL SINGLE LOCATION
INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP SINGLE LOCATION
TRIP RELEASE AMBIENT TEMP RATING 25.0 DEG CELSIUS NOMINAL SINGLE LOCATION
TRIP RELEASE CHARACTERISTIC TIME DELAY SINGLE LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 50.000 MAXIMUM AT 200 PCT SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 130.0 SINGLE LOCATION
RESET METHOD AUTOMATIC
BODY STYLE 16A SINGLE POLE TYPE
BODY LENGTH 1.891 INCHES NOMINAL
BODY WIDTH 1.188 INCHES NOMINAL
BODY HEIGHT 1.407 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 0.844 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 1.574 INCHES NOMINAL
CASE MATERIAL PLASTIC
MOUNTING FACILITY TYPE AND QUANTITY 2 UNTHREADED HOLE
UNTHREADED MOUNTING HOLE DIAMETER 0.174 INCHES NOMINAL
TERMINAL TYPE AND QUANTITY 2 QUICK DISCONNECT, FEMALE
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED CORROSION RESISTANT AND DUSTPROOF AND FUNGUS RESISTANT
MANUFACTURERS CODE 81349
NON-DEFINITIVE GOVERNMENT SPEC/STD REFERENCE MILC13516TYPE2GRADEACLASS1

Restrictions/Controls & Freight Information | NSN 5925-00-752-6903

Category Code Description
Hazardous Material Indicator CodePThere is no information in the HMIS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product
Demilitarization Code:ANon-Munitions List Item/ Non-Strategic List Item - Demilitarization not required.
Precious Metals Indicator Code:UPrecious metal type is unknown
Criticality Code:X The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
Category Code Description
No Freight Information