NSN 5925-00-642-0511 ETN5947, 00-642-0511, 006420511
Product Details | CIRCUIT BREAKER
5925-00-642-0511 A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.
Part Alternates: ETN5947, 5925-00-642-0511, 00-642-0511, 5925006420511, 006420511
Electrical and Electronic Equipment Components | Circuit Breakers
Supply Group (FSG) | NSN Assign. | NIIN | Item Name Code (INC) |
---|---|---|---|
59 | 01 JAN 1963 | 00-642-0511 | 00136 ( CIRCUIT BREAKER ) |
Cross Reference | NSN 5925-00-642-0511
Part Number | Cage Code | Manufacturer |
---|---|---|
ETN5947 | 30086 | SPD ELECTRICAL SYSTEMS, INC |
Request a Quote
What Our Customers Say
Compare
Related Products | NSN 5925-00-642-0511
Technical Data | NSN 5925-00-642-0511
Characteristic | Specifications |
---|---|
POLE QUANTITY | 3 |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 250.0 AMPERES AC AND 250.0 AMPERES DC ALL LOCATIONS |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 500.0 AC AND 250.0 DC ALL LOCATIONS |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 20000.0 AC AND 20000.0 DC ALL LOCATIONS |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 300.000 MINIMUM AT 200 PCT AND 900.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
RESET METHOD | MANUAL |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
BODY STYLE | 11B MULTIPOLE-SINGLE ACTUATOR TYPE |
BODY LENGTH | 11.000 INCHES NOMINAL |
BODY WIDTH | 9.000 INCHES NOMINAL |
BODY HEIGHT | 4.625 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 9.875 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.000 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 9.875 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.000 INCHES NOMINAL |
BOSS HEIGHT | 0.250 INCHES NOMINAL |
CASE MATERIAL | PLASTIC |
MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
UNTHREADED MOUNTING HOLE DIAMETER | 0.250 INCHES NOMINAL |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE TWO |
TERMINAL TYPE AND QUANTITY | 6 THREADED STUD AND 6 TAB W/SCREW |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | SHOCK RESISTANT AND VIBRATION RESISTANT |
FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE AND INTERCHANGEABLE TRIP RELEASE |
ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | 650.0 TO 1300.0 DC ALL LOCATIONS |
III ARC QUENCHING METHOD | AIR |
III STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
III PRECIOUS MATERIAL | SILVER |
III PRECIOUS MATERIAL AND | CONTACTS SILVER |
Restrictions/Controls & Freight Information | NSN 5925-00-642-0511
Category | Code | Description |
---|---|---|
Shelf-Life Code: | 0 | Nondeteriorative |
Hazardous Material Indicator Code | P | There is no information in the HMIS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product |
Demilitarization Code: | A | Non-Munitions List Item/ Non-Strategic List Item - Demilitarization not required. |
Controlled Inventory Item Code: | U | UNCLASSIFIED |
Precious Metals Indicator Code: | S | Item contains silver |
Criticality Code: | X | The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application. |
Category | Code | Description |
---|---|---|
NMF Description | 061300 | CIRCUIT BREAKER/SWITCH NOI |
Less than car load rating | ||
Less than truck load rating | P | 77.5 |
Water commodity Code | 658 | unknown |
Originating Activity Code | XX | |
Air Dimension Code | A | Shipment is not a consolidation and does not exceed 72 inches in any dimension. |
Air Commodity | H | Signal Corps supplies and equipment, including radio equipment and supplies, communications equipment and supplies, electrical equipment and supplies, etc. |
Air Special Handling | Z | No special handling required. |
Special Handling Code | 9 | unknonwn |
HAZMAT | ||
Type of Cargo | Z | No special type of cargo code applicable |
Management | NSN 5925-00-642-0511
Category | Code | Description |
---|---|---|
Cognizance Codes | 7H | Depot level reparable shipboard and base equipment, assemblies, components and repair parts related to Naval Sea Systems Command equipment Naval Inventory Control Point, Mechanicsburg |
Special Material Content | 9 | Non-Hazardous or Non-Sensitive Item, does not require hazardous or special handling, packaging or precautions |
Source of Supply | NRP | NAVICP-ERP 700 Robbins Avenue Philadelphia, PA 19111-5098 |
Agency | DN | Department of the Navy |
Service Organization | L | Lead Service - 22 (Repairable) |
Reparability | H | Depot Level Reparable |
Acquisition Advice Codes | C | SERVICE/AGENCY-MANAGED (Service/Agency use only.) # Issue, transfer, or shipment is not subject to specialized controls other than those imposed by individual Services supply policy. 1. The item is centrally managed, stocked, and issued. 2. Requisitions will be submitted in accordance with Service requisitioning procedures. |
Controlled Item Code | U | UNCLASSIFIED |
Shelf Life Code | 0 | Nondeteriorative |