Product Details | CIRCUIT BREAKER

5925-00-513-7610 A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.

Part Alternates: F461PC28, L6319482G8, TN231H4025AS1, 62013221919PC28, 6201-3221919PC28, 6319482G1925AMPTRIP, 6319482G19-25AMPTRIP, 5925-00-513-7610, 00-513-7610, 5925005137610, 005137610

Electrical and Electronic Equipment Components | Circuit Breakers

Supply Group (FSG) NSN Assign. NIIN
59 01 JAN 1963 00-513-7610

Drawings & Photos | NSN 5925-00-513-7610


Cross Reference | NSN 5925-00-513-7610

Part Number Cage Code Manufacturer
6201-3221919PC28 80064 NAVAL SHIP SYSTEMS COMMAND
6319482G19-25AMPTRIP 24446 GENERAL ELECTRIC CO
F461PC28 55615 SMITH-MEEKER ENGINEERING CO
L6319482G8 24446 GENERAL ELECTRIC CO
TN231H4025AS1 03497 GENERAL ELECTRIC CO OUTDOOR BREAKER BUSINESS SECTION

Request a Quote

What Our Customers Say

Compare

NSNs for Compare ( up to 4 ): Add 5925-00-513-7610

Technical Data | NSN 5925-00-513-7610

Characteristic Specifications
POLE QUANTITY 3
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 25.0 AMPERES AC AND 25.0 AMPERES DC ALL LOCATIONS
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 125.0 AC AND 125.0 DC ALL LOCATIONS
FREQUENCY IN HERTZ 60.0 ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 10000.0 AC AND 5000.0 DC ALL LOCATIONS
CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
TRIP RELEASE METHOD THERMAL-MAGNETIC ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS
TRIP RELEASE CHARACTERISTIC INSTANTANEOUS AND TIME DELAY ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 10.000 MINIMUM AT 200 PCT AND 180.000 MAXIMUM AT 200 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 138.0 ALL LOCATIONS
RESET METHOD MANUAL
MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
BODY STYLE 12B MULTIPOLE-SINGLE ACTUATOR TYPE
BODY LENGTH 5.000 INCHES NOMINAL
BODY WIDTH 4.750 INCHES NOMINAL
BODY HEIGHT 4.625 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 3.625 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 1.688 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 4.500 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 1.500 INCHES NOMINAL
BOSS HEIGHT 0.312 INCHES NOMINAL
CASE MATERIAL PLASTIC
MOUNTING FACILITY TYPE AND QUANTITY 2 UNTHREADED HOLE
UNTHREADED MOUNTING HOLE DIAMETER 0.250 INCHES NOMINAL
MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
ACTUATOR FUNCTION TRIP-RESET
ACTUATOR POSITION DESIGNATION AT POLE TWO
TERMINAL TYPE AND QUANTITY 6 QUICK DISCONNECT, FEMALE
AUXILIARY SWITCH FUNCTION AND QUANTITY 1 ALARM
SWITCH LOCATION AND POSITION DESIGNATION INTERNAL AT POLE TWO
SWITCH CONTACT ARRANGEMENT SINGLE POLE, DOUBLE THROW
SWITCH CURRENT RATING AND TYPE IN AMPS 10.0 AC AND 10.0 DC
SWITCH VOLTAGE RATING AND TYPE IN VOLTS 125.0 AC AND 125.0 DC
SWITCH TERMINAL TYPE SCREW

Restrictions/Controls & Freight Information | NSN 5925-00-513-7610

Category Code Description
Shelf-Life Code:0Nondeteriorative
Hazardous Material Indicator CodePThere is no information in the HMIS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product
Demilitarization Code:ANon-Munitions List Item/ Non-Strategic List Item - Demilitarization not required.
Controlled Inventory Item Code:UUNCLASSIFIED
Precious Metals Indicator Code:AItem does not contain precious metal
Criticality Code:X The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
Automatic Data Processing Equipment:0Represents items with no ADP components. NOTE: Codes 1 through 6 are only to be used when the item is Automatic Data Processing Equipment (ADPE) in its entirety and is limited to the type meeting only one of the definitions for codes 1 through 6. (See code 9)
Category Code Description
NMF Description 061300 CIRCUIT BREAKER/SWITCH NOI
Less than car load rating
Less than truck load rating P 77.5
Water commodity Code 658 unknown
Originating Activity Code XX
Air Dimension Code A Shipment is not a consolidation and does not exceed 72 inches in any dimension.
Air Commodity H Signal Corps supplies and equipment, including radio equipment and supplies, communications equipment and supplies, electrical equipment and supplies, etc.
Air Special Handling Z No special handling required.
Special Handling Code 9 unknonwn
HAZMAT
Type of Cargo Z No special type of cargo code applicable

Management | NSN 5925-00-513-7610

Category Code Description
Cognizance Codes9BNavy-owned stocks of DLA material
Naval Inventory Control Point, Mechanicsburg
Source of SupplySMSDefense Logistics Agency
Enterprise Business Systems
AgencyDNDepartment of the Navy
Service OrganizationNU.S. Navy
Acquisition Advice CodesXSEMIACTIVE ITEM-NO REPLACEMENT (NON-STOCKED ITEMS) A potentially inactive NSN which must be retained in the supply system as an item of supply because (1) stocks of the item are on hand or in use below the wholesale level and (2) the NSN is cited in equipment authorization documents TO & E, TA, TM, etc., or in-use assets are being reported. 1. Items are authorized for central procurement but not authorized for stockage at wholesale level. 2. Requisitions for in-use replacement will be authorized in accordance with individual Military Service directives. 3. Requisitions may be submitted as requirements generate. Repetitive demands may dictate an AAC change to permit wholesale stockage.
Controlled Item CodeUUNCLASSIFIED
Shelf Life Code0Nondeteriorative
Purchasing QTY
UOM
1
EA : Each