Product Details | CIRCUIT BREAKER

5925-00-336-1989 A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.

Part Alternates: JC3A3152, JC3-A3-15-2, 5925-00-336-1989, 00-336-1989, 5925003361989, 003361989

Electrical and Electronic Equipment Components | Circuit Breakers

Supply Group (FSG) NSN Assign. NIIN
59 24 DEC 1973 00-336-1989

Drawings & Photos | NSN 5925-00-336-1989


Cross Reference | NSN 5925-00-336-1989

Part Number Cage Code Manufacturer
JC3-A3-15-2 74193 EATON CORP HEINEMANN PRODUCTS

Request a Quote

What Our Customers Say

Compare

NSNs for Compare ( up to 4 ): Add 5925-00-336-1989

Technical Data | NSN 5925-00-336-1989

Characteristic Specifications
POLE QUANTITY 3
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 15.0 AMPERES AC ALL LOCATIONS
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 250.0 AC ALL LOCATIONS
FREQUENCY IN HERTZ 60.0 ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 1000.0 AC ALL LOCATIONS
CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
TRIP RELEASE METHOD MAGNETIC-HYDRAULIC ALL LOCATIONS
INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
TRIP RELEASE CHARACTERISTIC TIME DELAY ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 2.000 MINIMUM AT 200 PCT AND 22.000 MAXIMUM AT 200 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 ALL LOCATIONS
RESET METHOD MANUAL
MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
BODY STYLE 1C MULTIPOLE-MULTIPLE ACTUATOR TYPE
BUSHING LENGTH 0.098 INCHES MINIMUM AND 0.162 INCHES MAXIMUM
BODY LENGTH 1.968 INCHES MINIMUM AND 2.032 INCHES MAXIMUM
BODY WIDTH 1.468 INCHES MINIMUM AND 1.532 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 1.528 INCHES MINIMUM AND 1.592 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 0.718 INCHES MINIMUM AND 0.782 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 1.628 INCHES MINIMUM AND 1.692 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 0.718 INCHES MINIMUM AND 0.782 INCHES MAXIMUM
MOUNTING SURFACE TO TERMINAL END DISTANCE 1.898 INCHES MINIMUM AND 1.962 INCHES MAXIMUM
CASE MATERIAL PLASTIC
MOUNTING FACILITY TYPE AND QUANTITY 6 THREADED HOLE
THREAD SERIES DESIGNATOR UNC
NOMINAL THREAD SIZE 0.138 INCHES
THREAD QUANTITY PER INCH 32
MANUAL ACTUATOR TYPE AND QUANTITY 3 TOGGLE
ACTUATOR FUNCTION TRIP-RESET
ACTUATOR POSITION DESIGNATION AT EACH POLE
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT ONE, TWO, AND THREE LINKED
TERMINAL TYPE AND QUANTITY 6 QUICK DISCONNECT, MALE
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED DUSTPROOF
III ARC QUENCHING METHOD MAGNETIC BLOWOUT

Restrictions/Controls & Freight Information | NSN 5925-00-336-1989

Category Code Description
Hazardous Material Indicator CodePThere is no information in the HMIS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product
Demilitarization Code:ANon-Munitions List Item/ Non-Strategic List Item - Demilitarization not required.
Precious Metals Indicator Code:UPrecious metal type is unknown
Criticality Code:X The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
Category Code Description
NMF Description 061300 CIRCUIT BREAKER/SWITCH NOI
Less than car load rating P 77.5
Less than truck load rating P 77.5
Water commodity Code 658 unknown
Originating Activity Code ZG Germany
ZH
ZJ
Air Dimension Code A Shipment is not a consolidation and does not exceed 72 inches in any dimension.
Air Commodity H Signal Corps supplies and equipment, including radio equipment and supplies, communications equipment and supplies, electrical equipment and supplies, etc.
Air Special Handling Z No special handling required.
Special Handling Code 9 unknonwn
HAZMAT
Type of Cargo Z No special type of cargo code applicable