Product Details | CIRCUIT BREAKER

5925-01-278-7968 A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.

Part Alternates: KB3090, 5925-01-278-7968, 01-278-7968, 5925012787968, 012787968

Electrical and Electronic Equipment Components | Circuit Breakers

Supply Group (FSG) NSN Assign. NIIN
59 10 MAY 1988 01-278-7968

Drawings & Photos | NSN 5925-01-278-7968


Cross Reference | NSN 5925-01-278-7968

Part Number Cage Code Manufacturer
KB3090 89946 EATON CORPORATION

Request a Quote

What Our Customers Say

Compare

NSNs for Compare ( up to 4 ): Add 5925-01-278-7968

Technical Data | NSN 5925-01-278-7968

Characteristic Specifications
POLE QUANTITY 3
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 90.0 AMPERES AC ALL LOCATIONS
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 600.0 AC ALL LOCATIONS
FREQUENCY IN HERTZ 60.0 ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 900.0 AC ALL LOCATIONS
CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
TRIP RELEASE METHOD THERMAL-MAGNETIC ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS
TRIP RELEASE CHARACTERISTIC INSTANTANEOUS ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 ALL LOCATIONS
RESET METHOD MANUAL
MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
BODY STYLE 11B MULTIPOLE-SINGLE ACTUATOR TYPE
BODY LENGTH 10.000 INCHES NOMINAL
BODY WIDTH 4.125 INCHES NOMINAL
BODY HEIGHT 4.062 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 8.375 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 1.375 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 7.940 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 1.375 INCHES NOMINAL
BOSS HEIGHT 0.187 INCHES NOMINAL
CASE MATERIAL PLASTIC
MOUNTING FACILITY TYPE AND QUANTITY 4 UNTHREADED HOLE
UNTHREADED MOUNTING HOLE DIAMETER 0.281 INCHES NOMINAL
MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
ACTUATOR FUNCTION TRIP-RESET
ACTUATOR POSITION DESIGNATION AT POLE TWO
TERMINAL TYPE AND QUANTITY 6 COMPRESSION
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED FUNGUS RESISTANT
FEATURES PROVIDED ADJUSTABLE TRIP RELEASE
ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS 450.0 TO 900.0 AC ALL LOCATIONS
MANUFACTURERS CODE 89946
DESIGN CONTROL REFERENCE KB3090

Restrictions/Controls & Freight Information | NSN 5925-01-278-7968

Category Code Description
Hazardous Material Indicator CodePThere is no information in the HMIS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product
Demilitarization Code:BMunitions List Item - Mutilation (MUT) to the point of scrap required. (Formerly: Demilitarization not required. Trade Security Controls (TSCs) required at disposition.)
Precious Metals Indicator Code:AItem does not contain precious metal
Criticality Code:X The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
Category Code Description
No Freight Information